The MDR Power Supply Series supports inrush current protection of 30 A at 115 VAC and 60 A at 230 VAC. The series has an operating temperature range of -20 to 70°C and a three year warranty, which ensures suitability for operating in harsh environments.
In addition, the MDR Series has passed a 100% full load burn-in test, is UL/CUL listed, TÜV/CB certified, and CE marked. There are also models available with output ratings from 40 W to 60 W with 24 VDC output.
PACKAGE CONTENTS:
- Device: 1 x MDR-40-24
- Documentation: 1 x warranty card
Features
- High inrush current protection
- 24 VDC power output
- -20 to 70°C operating temperature range
- 85 to 264 VAC or 120 to 370 VDC input
Technical Specifications
Output Power Parameters
- Wattage:
- MDR-40-24: 40 W
- MDR-60-24: 60 W
- Voltage: 24 VDC
- Current Rating:
- MDR-40-24: 0 to 1.7 A
- MDR-60-24: 0 to 2.5 A
- Ripple and Noise: 150 mVp-p
- Voltage Adjustment Range: 24 to 30 VDC
- Setup/Rise Time at Full Load:
- 500 ms, 30 ms at 115 VAC
- 500 ms, 30 ms at 230 VAC
- Typical Hold Up Time at Full Load:
- 20 ms at 115 VAC
- 50 ms at 230 VAC
Input Power Parameters
- Voltage Range:
- 85 to 264 VAC (47 to 63 Hz)
- 120 to 370 VDC
- Typical Efficiency: 88%
- Typical Current:
- MDR-40-24: 0.7 A @ 230 VAC, 1.1 A @ 115 VAC
- MDR-60-24: 1.0 A @ 230 VAC, 1.8 A @ 115 VAC
- Typical Current (cold start): 60 A @ 230 VAC, 30 A @ 115 VAC
Overload Protection
- Rated Output Power: 105 to 150%
- Protection Type: Constant current limiting, recovers automatically after fault condition is removed
Overvoltage Protection
- Overvoltage Range: 31.2 to 36 V
- Protection Type: Shut down operating voltage, repower on to recover
Physical Characteristics
- Dimensions: 40 x 90 x 100 mm (1.57 x 3.54 x 3.94 in)
- Weight:
- MDR-40-24: 260 g (0.57 lb)
- MDR-60-24: 280 g (0.62 lb)
Environmental Limits
- Operating Temperature: -20 to 70°C (-4 to 158°F)
- Max. Operating Temperature at Full Load:
- MDR-40-24: 60°C
- MDR-60-24: 55°C
- Ambient Relative Humidity: 20 to 90% (non-condensing)
Standards and Certifications
- Safety:
- UL 508
- EN 62368-1
- IEC 62368-1
- EMC:
- EN 55032/35
- EN 61000-3-2 Class A
- EN 61000-3-3
- EN IEC 61204-3
- EN IEC 61000-6-2
- EMS:
- IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
- IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
- IEC 61000-4-4 EFT: Power: 2 kV
- IEC 61000-4-5 Surge: Power: 4 kV
- IEC 61000-4-6 CS: 0.15 kHz to 80 MHz: 10 Vrms
- IEC 61000-4-8 PFMF: 30 A/m
- IEC 61000-4-11
Warranty
- Warranty Period: 3 years
- Details See www.moxa.com/warranty